31
5. The following message will be displayed “Do
you want to enter a reference volume for the
autocalibration?”
6. Select OK and enter a reference volume to start.
The reference volume needs to be slightly less
than the current volume.
After the reference volume is entered, the tank should
have an ACTIVE indication in the (FMS) / Autocalibration
(Tank) screen.
Note:
If Autocal stops collecting points for any reason, stop
it, reprogram the original tank chart, and start over.
Reasons Why Autocal Would Stop
• Power failure
• Setup entered
• Probe failure
• TS-DIM failure
• Delivery in Tank under Autocal.
Autocal Completion
1. The Autocalibration procedure will stop when the
Percent Coverage is reached.
2. Monitor the Daily Reconciliation and Delivery
Reports for a few weeks to ensure that they are
within tolerance.