Displayed Alarm /
Warning
Device Description Recommended Actions
SN3 Sump Full ChannelSN3 3-wire sensor detected
sump full of liquid.
Visually inspect location carefully for presence of liquid. In the case of
a leak, follow site policy procedures. If no liquid is present, and alarm
still exists, sensor may be tripped on error. Check wiring continuity from
sensor to console. Test sensor a
SN3 Sync Error ChannelSN3 3-wire sensor data signals
not in sync with module.
Verify correct wiring.
SN3 Vapor ChannelSN3 3-wire discriminate sensor
detecting vapors at location.
Visually inspect area for product presence.
SN3 Water ChannelSN3 3-wire discriminate sensor
detecting water at location.
Visually inspect area for water presence.
Sudden Pressure Loss Line System detected sudden
pressure loss in line.
Follow site procedures for line leaks.
System Bus Error None Data transfer errors
occurred in the System
Bus. Suspect Bus at fault,
test and replace if found to
be inoperable.
Contact Franklin Fueling Systems’ Technical Services Dept. for support
on this issue. Follow safety procedures before working inside the cons
System memory error Tank Console memory at fault. Contact Franklin Fueling Systems for support.
System Setup Error None Errors in the setup of the
system programming.
The console may need to be reprogrammed.
Tank Gross Leak Detected Tank Tank Gross leak test
detected tank. Suspect
possible leak.
Review tank leak test history and programming. Refer to Section
5: Misc./ Tank Leak Tests – Type and Frequency for instructions on
manually starting line leak tests.
Tank Leak Detected Tank Tank leak detected. Suspect
possible leak.
Review tank leak test history and programming. Refer to Section
5: Misc./ Tank Leak Tests – Type and Frequency for instructions on
manually starting line leak tests.
Tank SCALD Leak Detected Tank SCALD leak test detected
tank leak. Suspect possible
leak.
Review tank leak test history and programming. Review, why tank tests
fail (see …).
Tank Theft Detected Tank Product used in Sentinel
Mode exceeds theft limit
set. Suspect theft, and
then verify theft limit in
programming.
Verify theft limit in programming. Also obtain an accurate product level
and compare to inventory.
Temperature error Tank Special Probe RTD
temperature error detected.
Verify correct RTD table programming. If problem still exists, suspect
wiring or faulty probe.
Ullage error Tank Ullage reported has
exceeded tank capacity.
Verify correct Tank Chart programming.
Unstable probe Tank LL Liquid Level probes can
send inconsistent data back
to console.
Test probe communications by connecting the probe directly to the
console.
Water volume error Tank Water volume has
exceeded tank capacity.
Verify actual water volume. Verify programming as well.