Fuel Management System
Programming Guide
T5 Series
Software Revision 1.7.4
Franklin Fueling Systems • 3760 Marsh Rd. • Madison, WI 53718 USA
Tel: +1 608 838 8786 • 800 225 9787 • Fax: +1 608 838 6433 • www.franklinfueling.com
Zobrazit stránku 0
1 2 3 4 5 6 ... 65 66

Shrnutí obsahu

Strany 1 - Fuel Management System

Fuel Management SystemProgramming GuideT5 SeriesSoftware Revision 1.7.4 Franklin Fueling Systems • 3760 Marsh Rd. • Madison, WI 53718 USATel: +1 608

Strany 2 - Warranty Information

6Password Login1. Press the User Roll icon 2. Enter Password for the desired level as described in the Access Control section on page 5.Default pas

Strany 3 - Contents

7Conguring IP Settings for CommunicationBefore attempting to modify any computer settings, contact the Information Technologies department of your bu

Strany 4

8• In Classic View, click on Network Connections.4. Right-click on Local Area Connection and select Properties.5. In the Local Area Connection Prope

Strany 5 - Important Safety Messages

9Obtain an IP Address AutomaticallyComputers commonly use this setting to obtain an IP address automatically. 1. If Obtain an IP address automaticall

Strany 6 - Approvals

10Connecting a PC to the T5 series RS-232 PortCOMM 1 is used to connect a PC or laptop with the console via the Web Browser Interface for programming

Strany 7 - Introduction

115. Enter a Computer Name (it can be the site name).6. Select the communication port to be used from the Select a Device drop-down list.7. Select

Strany 8 - Related Documentation

1210. Under the General tab, select Congure. 11. Change the Maximum speed (bps) to 57600.12. Disable all of the Hardware Features and click OK.13.

Strany 9 - User Interfaces (UI)

1319. In the Type of dial-up server I am calling, select PPP: Windows 95 / 98 / NT4 / 2000, Internet from the drop-down list then click OK.Check Oper

Strany 10 - Modifying Passwords

14Conguration and PreferencesConguration and Preferences include how information will be displayed and conguring the console for its location and c

Strany 11

15Numbers OptionsDigit groupingGroup digits by 103 using specied symbol (i.e. either “123456789” or “123,456,789”).Digit grouping symbol Symbol used

Strany 12

iiCopyright ©2011 by Franklin Fueling Systems. No part of this publication may be reproduced in any form without the prior written consent of FFS. All

Strany 13 - Check Status of Connection

16Conguration MenuConguration OptionsUsing the options in this menu, you can change:• Console passwords • COM 1 parameters• Network parameter

Strany 14 - Communication

17Time ZoneSet the Time Zone according to your geographical location. If your choice does not appear on the rst screen, use the navigation up and dow

Strany 15

18Programming and NavigationConsole NavigationThe operating system is designed for easy navigation. Applications allow the user to modify programming

Strany 16

19Character Navigation ButtonsWhen prompted to enter system information, press the corresponding keys.Character Selection: Selects between upper case

Strany 17 - Initial Console Conguration

20Programming System ParametersUsing the touch screen function of the console to program, navigate from the Home Status screen by pressing the Main Me

Strany 18 - Conguration and Preferences

21Programming ModulesThe Fuel Management System is composed of a custom set of modules. Each module maintains individual characteristics. Parameters m

Strany 19

22Probe ModulesThe Probe Module gather data from probes, vapor ow meter and TS-DMS sensors. This information is processed by the Controller Module fo

Strany 20 - Conguration Menu

234-20 mA and 4-20 mA EXP Input Modules The Analog Input Module has 8 identical channels for loop powered IS sensors with a 4-20 mA interface. The 4-

Strany 21 - Serial Port (Comm 1)

24Power Supply ModuleThe Power Supply is a non-intrinsically safe module that provides power to the T5 series console from line voltage rated 110 - 24

Strany 22 - Programming and Navigation

25Group Name Parameter NameParameter DefaultDescriptionParameter InputRS-232 Baud Rate (9600) Data transmission speed in bits per second. 1200-5760

Strany 23 - Application Menus

iiiContentsNotice...iiI

Strany 24 - Programming System Parameters

26Relay ModulesThe Relay Module is a non-intrinsically safe module that has 8 identical Form C output channels. Each channel has a fuse and three term

Strany 25 - Programming Modules

27Dispenser InterfaceThe Dispenser Interface is used in VRM and Reconciliation applications to communicate sales data from the dispensers to the conso

Strany 26

28Programming FMS ParametersHere is where specic equipment parameters will be modied to match the site setup.Fuel Management SystemGroup Name Parame

Strany 27

29FMS Parameters ContinuedGroup Name Parameter NameParameter DefaultDescriptionParameter InputFuel Management System Special Tanks Special # Sh

Strany 28

30Group Name Parameter NameParameter DefaultDescriptionParameter InputSpecial ProductsSpecial NCorrection Type (Table 6A) As dened by the fuel provid

Strany 29

31Group Name Parameter NameParameter DefaultDescriptionParameter InputReconciliationOver Short Limit Percent (1.00%) Gives the allowed amount on varia

Strany 30 - Relay Modules

32E-MailGroup Name Parameter NameParameter DefaultDescriptionParameter InputE-Mail “From” [email protected] of sender (console)

Strany 31

33Web Browser InterfaceNavigating Applications RemotelyThe Web Browser Interface offers several ways to navigate through applications: • Easy-to-rea

Strany 32 - Programming FMS Parameters

34Backup Setup FilesDownloadBackup allows you to download the setup le and store it on any PC connected to the console. This le can be uploaded to t

Strany 33 - Manifold Tank System

35UploadWhen required, the backup conguration le will need to be reloaded onto the console to restore a previous setup. When uploading, it is import

Strany 34

ivProgramming Parameters ... 28Fuel Manage

Strany 35 - Vapor Recovery Monitoring

36Leak TestingAll T5 series console models meet (or exceed) the requirements of the U.S. Environment Protection Agency (EPA / 530 / UST-90 / 006 test

Strany 36 - System Sentinel Anyware

37Manually Forcing Static Leak Tests1. To force a Static Tank Leak test, press the FMS button in the Application Window.2. Press the Application Men

Strany 37 - Web Browser Interface

38Tank Leak Test ResultsLeak test results are either increase, passed, failed, or indeterminate.Reasons Why Tank Leak Tests Fail• The tank leaks.•

Strany 38 - Backup Setup Files

39TS-LS500 Auto Learn Line Leak TestingOverviewA 0.2 gph and a 0.1 gph test line leak tests can be started from the console. Some jurisdictions recomm

Strany 39

40DTU (Data Transfer Unit) Setup and Programming1. Under Setup / System Conguration/Modules Expected, set Console DTU to 1.2. Under Setup, locate R

Strany 40 - Leak Testing

419. Under Setup/4-20mA Input Modules (DTU) / locate Remote Module 2 and enter the number of DTUs installed. The maximum number of channels per a 4-2

Strany 41

42DIM Programming1. For Web Browser programming capability, connect a computer to the T5 series tank gauge. (See programming section of this manual f

Strany 42 - SCALD Tank Leak Tests

4311. Communication refers to the method of communication used by the corresponding distribution box.Some typical examples:• Current loop-Gilbarco P

Strany 43

4415. Under Dispenser Interface, select Fueling Points.Note: A Fueling Point is anywhere a vehicle can stop and dispense fuel. Most dispensers have

Strany 44

45There are two ways to program the Hose Position:• Manually-If you know the D-Box grade position you can manually select the Position number from th

Strany 45

1Important Safety MessagesFFS equipment is designed to be installed in association with volatile hydrocarbon liquids such as gasoline and diesel fuel.

Strany 46 - DIM Programming

46Dual DIM InstallationSome sites and dispenser congurations may require the use of a second DIM module that would be installed externally to perform

Strany 47

47TS-TPI Overview and Functionality Tank fuel management can be achieved using a Franklin Fueling Systems T5 Series Fuel Management Systems and an

Strany 48

48TPI SetupGroup Name Parameter NameParameter DefaultDescription Max ValuePower Supply RS-485TS-TPIEnable Interface (Yes)E

Strany 49

49List of Alarms and TroubleshootingFor all alarms conditions, the troubleshooting steps provided in this chapter are suggested actions to take in the

Strany 50 - Communication Settings

50Displayed Alarm / Warning Device Description Recommended ActionsConsole DTU is ofine Slot The Console DTU is not communicating with the ConsoleChe

Strany 51 - TS-TPI Overview

51Displayed Alarm / Warning Device Description Recommended ActionsRelay module number mismatchslot Relay Modules detected does not match the number pr

Strany 52 - TPI Setup

52Displayed Alarm / Warning Device Description Recommended ActionsVFM No Data VRMThe Vapor Flow Meter is detected but is not communicating with the Co

Strany 53 - System Alarms

53Displayed Alarm / Warning Device Description Recommended ActionsHigh product volume Tank The specied tank has reached the programmed High Product V

Strany 54 - Warning

54Displayed Alarm / Warning Device Description Recommended ActionsManifold low low product volumeTank The specied manifold has reached the programmed

Strany 55 - VRM Alarms

55Displayed Alarm / Warning Device Description Recommended ActionsSCM AlarmsContainment Not Learned SCM The learning process has not been completed.Re

Strany 56 - FMS Alarms

2Certied Programmer/Service Person: Only an FFS certied programmer or service person is allowed to access both the user interface keypad and areas i

Strany 57

56Displayed Alarm / Warning Device Description Recommended ActionsSN3 Pwr Short Slot 3-Wire sensor malfunction. If a 2-Wire sensor is used on a 3-wire

Strany 58

57Displayed Alarm / Warning Device Description Recommended ActionsLine Not Learned Line Specied line not learned. Complete learn process, if any lear

Strany 59 - Wire Sensor Alarms

58Displayed Alarm / Warning Device Description Recommended ActionsPump Communication Fail TPI Communication from the TPI to the STP controller has fai

Strany 60

59Appendix A - Standard Tanks TableLegendO/C = Owens Corning / FC Fluid ContainmentD = Diameter (Dia.)L = LengthS = Single WallDW = Double Wall Tank (

Strany 61 - TPI Alarms

60Type #Manufacturer Model Capacity (Gallons)DimensionsD x L (inches)S / DW Wall27 Xerxes — 3,000 96 x 147 S28 Xerxes — 4,000 75 x 263 S29 Xerxes —

Strany 62 - Printer Alarms

61Appendix B - Standard Products Table Product Name API Gravity (6B Compensation)Leaded Regular 63.5Unleaded Regular 63.5Unleaded Plus 62.8Unleaded Ex

Strany 63

©2011 FFS 000-2142 Rev. E

Strany 64

3IntroductionThe purpose of this manual is to guide installers, operators and technicians through programming and troubleshooting the T5 series consol

Strany 65

4Denitions and AcronymsModule – A module is a plug-in card within the T5 series console that is used to perform various functions of the console. The

Strany 66 - ©2011 FFS 000-2142 Rev. E

5GeneralAfter the Fuel Management System has been installed, typically your interaction with the system will be from the LCD display, on-board printer