Appendix B – Alarm Table
Note: Refer to Safety Instructions outlined in this manual prior to performing any maintenance on or inside the console.
Note: If at any time while troubleshooting a Warning or Alarm this guide does not correct the issue, contact FFS Technical 
Services.
Warning
Always remove power from the console prior to installing or removing a module or performing any
maintenance while the console door is open.
System
Displayed Warning Description Recommended Actions Reference Source
2-Wire Sensor Module
Is Ofine
The specied 2-Wire Sensor Module 
listed with the alarm has experienced 
a problem or may not be recognized 
by the Controller Module.
Cycle power to the console. Visually 
verify that the green ‘RUN’ light on the 
applicable 2-Wire Sensor Module is on 
continuously after the system boot is 
complete.
Installation Guide / 
Applicable Bulletins*
2-Wire Sensor Module
Number Mismatch
The number of expected 2-Wire 
Sensor Modules does not equal the 
number of 2-Wire Sensor Modules 
installed.
Verify the physical number of 2-Wire 
Sensor Modules installed and compare 
with the number of 2-Wire Sensor 
‘Modules Expected’ in the programming.
General Setup in
Programming Manual
 / Applicable Bulletins*
3-Wire Sensor Module
is Ofine
The specied 3-Wire Sensor Module 
listed with the alarm has experienced 
a problem or may not be recognized 
by the Controller Module.
Cycle power to the console. Visually 
verify that the green ‘RUN’ light on the 
applicable 3-Wire Sensor Module is on 
continuously after the system boot is 
complete.
Installation Guide / 
Applicable Bulletins*
3-Wire Sensor Module
Number Mismatch
The number of expected 3-Wire 
Sensor Modules does not equal the 
number of 3-Wire Sensor Modules 
installed.
Verify the physical number of 3-Wire 
Sensor Modules installed and compare 
with the number of 3-Wire Sensor 
‘Modules Expected’ in the programming.
General Setup in
Programming Manual
/ Applicable Bulletins*
4-20mA Input Module
Error
Input amperages have exceeded their 
thresholds—this Error applies to the 
4-20mA Input Module listed with the 
alarm.
Troubleshoot external 4-20mA device and 
wiring from the module and channel of the 
4-20mA Input Module listed with the alarm. 
Applicable Equipment 
Guide(s)*
4-20mA Input Module
is Ofine
The specied 4-20mA Input Module 
listed with the alarm has experienced 
a problem or may not be recognized 
by the Controller Module.
Cycle power to the console. Visually 
verify that the green ‘RUN’ light on the 
applicable 4-20mA Input Module is on 
continuously after the system boot is 
complete.
Installation Guide / 
Applicable Bulletins*
4-20mA Input Module
Number Mismatch
The number of expected 4-20mA Input 
Modules does not equal the number of 
4-20mA Input Modules installed.
Verify the physical number of 4-20mA
Input Modules installed and compare with 
the number of 4-20mA Input ‘Modules 
Expected’ in the programming.
General Setup in
Programming Manual
/ Applicable Bulletins*
AC Input Module
is Ofine
The specied AC Input Module listed 
with the alarm has experienced a 
problem or may not be recognized by 
the Controller Module.
Cycle power to the console. Visually 
verify that the green ‘RUN’ light on 
the applicable AC Input Module is on 
continuously after the system boot is 
complete.
Installation Guide / 
Applicable Bulletins*
AC Input Module
Number Mismatch
The number of expected AC Input 
Modules does not equal the number of 
AC Input Modules installed.
Verify the physical number of AC Input 
Modules installed and compare with the 
number of AC Input ‘Modules Expected’ in 
the programming.
General Setup in
Programming Manual
/ Applicable Bulletins*
IO Input Alarm The input senses either voltage pres-
ent or no voltage. This alarms when 
input voltage is not as programmed
Verify that programming parameters 
meet site specication. Check all wiring 
associated with the input at fault.
Installation Guide / 
Applicable Bulletins*
IO Module Number
Mismatch
The number of expected IO modules 
does not equal the number of IO 
modules installed
Verify the physical number of IO modules 
installed and compare with the number of 
IO modules programmed.
Installation Guide / 
Applicable Bulletins*
* Bulletins and the T5 Series Installation Guide (p/n 000-2150) and the T5 Series Programming Manual (000-2142) can be found on 
Franklin Fueling’s web site - http://www.franklinfueling.com/service/.   Select Technical Documentation / Fuel Management Systems