Test Result Alarms
Test Result Condition Possible Cause Resolution
Pass Line is tight
Fail Actual Leak Line pressure variations are outside 
threshold
Check for leaks, force leak test 
to verify
Temperature Instability Temperature uctuations cause 
pressure variances
Check for leaks, force leak test 
to verify
Inadequate learning Line not properly bled to zero during 
learning
Re-learn the line, follow 
procedures
Air was not bled out of the line prior 
to learning
Purge the line, re-learn
Air in line Line left open or air elimination loop 
failing
Purge the line 
Abort (no 
indication)
Dispensing A hook signal was detected, this 
resets the testing 
Allow test cycle to complete 
before dispensing
Line disabled Either manually, or by another 
application shut the STP down
Check other alarms, nd source 
of interruption
Manual test started User forced a line leak test Cycle resets after manual test 
completes
STP Shutdown 2 consecutive 3 GPH test 
failures
Possible gross leak Investigate, then Force a 
Manual Gross Test
1-2 consecutive 0.2 GPH 
test fails (depending on 
programming)
Possible 0.2 GPH leak Investigate, then Force a 
Manual Monthly Test
1-3 consecutive 0.1 GPH 
test fails (depending on 
programming)
Possible 0.1 GPH leak Investigate, then Force a 
Manual Annual Test
3 consecutive catch pressure 
tests that over 50 psi
High line pressure Investigate, adjust or replace 
check valve or functional 
element
Catch pressure test failure Pressure was less that 12 psi after 
programmed delay when STP 
turned off 
Investigate, force a manual test 
and observe pressure
Pressure up test failure Pressure was less that 12 psi after 
programmed delay when STP 
turned on
Investigate, force a manual test 
and observe pressure
Clearing Alarms
Clearing a console of alarms is important because, depending on how the T5 Series FMS console has been set up, 
alarms can: disable channels, start an annunciator, or stop a line test under way.
Administrator privileges will be necessary to clear line alarms on the T5 Series FMS console. For instructions on how to 
obtain an Administrator access level, please refer to the T5 Series FMS Programming Guide (p/n 000-2142) or the TS-
550evo FMS Programming Guide (p/n 000-2173).
1.  Identify the alarm on the FMS Alarms screen.
2.  Diagnose the condition using information found in the Alarms chapter of this guide.
3.  Follow the troubleshooting steps in the previous section of this chapter to correct the issues indicated by the alarms.
4.  Navigate to the Line Control screen.
5.  Select Reset Alarms on the Control screen. 
6.  Select Enable/Disable on the Control screen if you were not given the choice to enable the line when the alarms were 
reset.
If the condition still exists, the alarm can take up to several hours to reappear after the line is enabled. 